| RMS Voltage |
The effective AC voltage over a selected measurement interval. |
Nominal system voltage; commonly 120 V or 230 V in low-voltage systems. |
Persistent undervoltage or overvoltage can cause overheating, malfunction, or reduced motor torque. |
Compare measurements with the nominal voltage and the applicable supply standard or installation limits. |
| Voltage Sag |
A short-duration reduction in RMS voltage, typically lasting from about 0.5 cycle to one minute. |
Voltage reduced to approximately 10%–90% of nominal. |
Large motors starting, transformer energization, short circuits, or overloaded feeders. |
Check event timing against motor starts, feeder loading, and upstream fault records. |
| Voltage Swell |
A short-duration increase in RMS voltage, typically lasting from about 0.5 cycle to one minute. |
Voltage increased to approximately 110%–180% of nominal. |
Sudden load disconnection, incorrect voltage regulation, or single-phase faults. |
Review switching events and regulator settings; assess sensitive electronic equipment exposure. |
| Voltage Interruption |
A temporary or sustained loss of supply voltage below the analyzer’s event threshold. |
Near-zero RMS voltage during the event. |
Breaker operation, utility faults, loose connections, or equipment shutdown. |
Use event duration and phase information to distinguish an upstream outage from a local connection problem. |
| Frequency |
The rate at which the AC waveform completes cycles. |
Usually 50 Hz or 60 Hz, depending on the electrical system. |
Generator control issues, weak-grid conditions, or major generation-load imbalance. |
Evaluate deviations over time rather than relying on a single instantaneous reading. |
| Voltage Unbalance |
The difference among phase voltages, often calculated using negative-sequence voltage. |
A balanced three-phase system has equal phase magnitudes and approximately 120° phase separation. |
Unequal loads, poor connections, blown fuses, or distribution-system faults. |
Investigate phase loading and terminals; even small voltage unbalance can increase motor heating. |
| Current Unbalance |
The difference among phase currents in a three-phase circuit. |
Phase currents should be similar under balanced loading. |
Uneven single-phase loads, motor winding problems, or supply-voltage unbalance. |
Compare phase currents with equipment ratings and verify whether the imbalance is load-related or supply-related. |
| Total Harmonic Distortion (THD) |
The combined effect of harmonic components relative to the fundamental voltage or current. |
No universal limit applies to every installation; limits depend on the network and applicable standard. |
Variable-frequency drives, switched-mode power supplies, rectifiers, or overloaded transformers. |
Review individual harmonic orders, not only the total percentage, and assess heating or interference risks. |
| Power Factor |
The ratio of real power to apparent power, including the effect of phase shift and waveform distortion. |
A value close to 1.00 indicates efficient use of apparent power. |
Inductive motors, transformers, lightly loaded equipment, or harmonic-producing loads. |
Separate displacement power factor from true power factor before selecting corrective equipment. |
| Inrush Current |
The brief current surge that occurs when equipment is energized or a motor starts. |
Highly dependent on equipment design, motor size, transformer characteristics, and starting method. |
Nuisance trips, voltage sag, contact wear, or undersized conductors and protective devices. |
Correlate the current waveform with voltage sag and verify protective-device coordination. |
| Transient Voltage |
A rapid, short-lived change in voltage caused by switching or electrical disturbances. |
No single acceptable amplitude applies to all installations; duration, source, and equipment withstand are important. |
Lightning, capacitor switching, inductive load switching, or poorly suppressed coils. |
Use a sufficiently high sampling rate and suitable probes; inspect surge protection and switching circuits. |
| Flicker |
Low-frequency voltage fluctuations that may produce visible lamp brightness changes. |
Evaluated using standardized short-term and long-term flicker indices. |
Arc furnaces, welders, large motors, compressors, or rapidly varying industrial loads. |
Identify the fluctuating load and compare results with the applicable flicker limits. |
| Waveform Capture |
Time-based records of voltage and current before, during, and after an event. |
A stable sinusoidal waveform with the expected phase relationship for the circuit. |
Clipping, notching, distortion, phase loss, loose connections, or switching disturbances. |
Use the waveform together with RMS trends, event timestamps, and harmonic data to confirm the cause. |